KB58578
Published: December 12, 2007
Revision: 4.0

'Move I/O Unit to Numeric Table' PAC Control command causes intermittent error -3


Applies To:

SNAP-PAC-S1
SNAP-PAC-R1
SNAP-PAC-R2
SNAP-UP1-ADS
SNAP-UP1-M64
SNAP-UP1-D64
SNAP-LCE

Versions Affected:

Problem was discovered in version: R8.0e SNAP PAC control engines, R7.2d Ultimate I/O control engines


Problem is fixed in version: R8.0f SNAP PAC control engines, R7.2h Ultimate I/O control engines

Resolved In Version:

Problem is fixed in version: R8.0f SNAP PAC control engines, R7.2h Ultimate I/O control engines


Symptoms:

When using the Move I/O Unit to Numeric Table command in a PAC Control strategy, a possible "‑3 Buffer overrun or invalid length error." error message may be posted to the control engine error queue.


Workaround:

Instead of using the command:

    MoveIoUnitToNumTable(I/O Unit, Starting Index, Table)

use the command:

    MoveIoUnitToNumTableEx(I/O Unit, Table, Starting Index, Points per Module)

Notice the commands call the Table and Starting Index parameters in reverse order.


Resolution:

Opto 22 has resolved this issue.


Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2024 Opto 22. All rights reserved.