G4A8R, G4RAX, and B200 analog points are always scaled for degrees Celsius in PAC Control/ioControl


Applies To:

PAC Control Professional
ioControl Professional
G4A8R
G4RAX
B200

Versions Affected:

Problem was discovered in version: ioControl R7.1d
PAC Control R8.0a

Resolved In Version:

R10.0a


Symptoms:

When Mistic analog temperature input modules are configured for degrees Fahrenheit in PAC Control or ioControl, the configuration dialog still indicates degrees Celsius. 

Workaround:

This is a known issue that affects Mistic analog points in PAC Control and ioControl. In Debug mode, the values shown are the correct degrees Fahrenheit values.

No engineering unit scaling is necessary. The scaling is part of the linearization that occurs in the brain and does not need to be changed.

Resolution:

Opto 22 has resolved this issue.

Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2024 Opto 22. All rights reserved.