Updated bootloader available for SNAP-PAC-S1
Revision:  2.0
Published:  9/20/2011
Applies To
SNAP-PAC-S1
Versions
Any loader version prior to:  
R3.1c

DESCRIPTION

An updated bootloader (loader) for the SNAP-PAC-S1 is available for controllers with loaders prior to version R3.1c. The update is required and is recommended for your next maintenance opportunity.

To update the bootloader, a special update firmware file has been designed to provide a convenient and simple upgrade. Bootloader update kernel version S8.0g, evaluates the installed SNAP-PAC-S1 bootloader and updates it to version R3.1c, if necessary.

Perform the instructions as described in the following procedure.

PROCEDURE

To upgrade the loader, follow these steps, taking care not to interrupt the installation process by turning off power to the controller. Doing so may render the controller inoperable, requiring the controller be sent to the factory for repair.

  1. Download the special bootloader update file from here.
  2. Because installing the special firmware removes the existing firmware on the controller, make sure a copy of the firmware to be re-installed is available. For example, if the SNAP-PAC-S1 is running firmware version R8.0e, verify you have the snap‑pac‑s1‑r8.0e.bin file. If the firmware file is no longer available from the Opto 22 web site, contact Opto 22 Product Support to obtain the desired version.
  3. From PAC Manager, select Tools→Install Firmware via Ethernet.
  4. From the I/O Unit Maintenance window, highlight the Install Firmware command, navigate to where the special S8.0g firmware file is located, and select it. Add the controller's IP Address.
  5. Do not turn power off to the controller during the next steps.
  6. Click the Execute button. The S8.0g firmware file installation begins.
  7. After the S8.0g firmware file is installed, the SNAP-PAC-S1 will automatically reboot. Two fast green blinks indicate the SNAP‑PAC‑S1 is booting.
  8. The bootloader update process takes several seconds. During this time, the status LED is turned off.
  9. When the bootloader update process is complete, the STAT LED blinks once per second. The LED color indicates the outcome of the update:

  10. Green: The loader was successfully updated to version R3.1c.
    Orange: The loader did not need to be updated.
    Red: The SNAP-PAC-S1 no longer boots. Contact Opto 22 Product Support.

  11. Use PAC Manager and repeat steps 2 and 3 to re-install firmware . Substitute the name of the desired controller firmware file instead of the special firmware file.
  12. The controller is ready to resume normal operation.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None