Modbus/TCP, IO4AB, and SNMP 4-channel data may be old
Revision:  3.0
Published:  12/22/2011
Applies To
Firmware for:
SNAP-PAC-R1
SNAP-PAC-R2
SNAP-PAC-R1-W
SNAP-PAC-R2-W
SNAP-PAC-EB1
SNAP-PAC-EB2
SNAP-PAC-EB1-W
SNAP-PAC-EB2-W
SNAP-PAC-SB1
SNAP-PAC-SB2
Versions
Problem affects versions:  
R8.1a through R9.1c
Problem is fixed in version:  
R9.1d

SYMPTOMS

Four-channel digital input and output states and/or feature values (such as counter values) may stop updating This can first occur 24.85 days after the unit was powered up. It can then occur at 49.7 day intervals after that.

The problem does not occur when using OptoMMP protocol to communicate with the I/O unit, such as when a SNAP-PAC controller or OptoOPCServer communicates with the I/O unit. It is only possible for this problem to occur when using the following protocols, while not using OptoMMP protocol:

  • Modbus/TCP
  • Ethernet/IP
  • SNMP

DIAGNOSIS

This condition may be diagnosed using PAC Manager.

  1. Perform an Inspect (Tools > Inspect) and Status Read of the I/O unit. Note the value of the 4-Channel Digital Scan Count field.
  2. Wait a couple seconds and Refresh the window.
  3. See if the 4-Channel Digital Scan Count field significantly changes in value (should change at a rate of 200 Hz or faster). If the value is the same or is very slowly changing, this problem may be occurring.

CASE STATUS

Opto 22 has resolved this issue.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None