PAC Control: Analog points higher than the 4th point on a SNAP-PAC-R1-B I/O unit show incorrect values


Applies To:

PAC Control Basic
PAC Control Professional

Versions Affected:

Versions affected: R9.4c through R9.6b
Problem is fixed in version: R9.6c

Resolved In Version:

Problem is fixed in version: R9.6c


Symptoms:

Note: This issue is related to PAC Control software, not to the SNAP-PAC-R1-B firmware or hardware. 

If your strategy includes a SNAP-PAC-R1-B I/O unit that has an analog I/O module with more than 4 points (such as the SNAP-PAC-AITM-8), points higher than the 4th point will show incorrect values. When you inspect these points in Debug mode, PAC Control shows the XVAL as either 0 (zero) or  -1.#QNAN.

Workaround:

As a temporary fix, when you configure the I/O unit, select SNAP-PAC-R1 instead of SNAP-PAC-R1-B. Then, configure its points as normal.

CAUTION: If you use this workaround, don't forget that the I/O unit is really a SNAP-PAC-R1-B, which does not accept 4-channel digital modules in positions higher than 7 on the rack. Make sure you do not place 4-channel digital modules in the upper 8 module positions. 

Resolution:

Opto 22 has resolved this issue.

Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2024 Opto 22. All rights reserved.