Re-enabled SNAP-PAC-S1 redundant ports cannot re-enable SNAP-PAC-R1
Revision:  2.0
Published:  3/2/2007
Applies To
SNAP-PAC-S1 Controller Firmware
Versions
Problem was discovered in version:  
R7.1d
Problem is resolved in version:  
R8.0a

SYMPTOMS

The SNAP-PAC-R1 I/O unit cannot be re-enabled after both the primary and secondary Ethernet ports on a SNAP-PAC-S1 were disabled, and then re-enabled.

RESOLUTION

Opto 22 has resolved this issue.

MORE INFORMATION

From ioControl Professional, this is recreated by doing the following:

  • Create an empty strategy with a redundant SNAP-PAC-R1 I/O unit configured. Both IP addresses are enabled.
  • From Debug mode, run the empty strategy, then open an Inspect window for the I/O unit.
  • From the Inspect window, remove the check from Primary Address. The unit switches to the Secondary Address.
  • Remove the check from Secondary Address. The I/O unit is disabled and a warning is put into the controller error queue.
  • Check the Enabled box for the Primary Address.
  • Set ‘Communication Enabled’ for the I/O unit to "Yes" and hit "Apply.”
  • The unit is not enabled and an error is placed in the controller error queue.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None