Downloading and starting an ioControl strategy with PIDs on Ethernet-based I/O units, may cause outputs to spike
Revision:  2.0
Published:  9/5/2006
Applies To
Firmware for:
SNAP-PAC-R1
SNAP-PAC-R2
SNAP-UP1-ADS
SNAP-UP1-M64
SNAP-B3000-ENET
Versions
Behavior is present in version:  
R7.1a

SYMPTOMS

A PID output with a host-based setpoint on Ethernet-based I/O units, may spike when a just-downloaded ioControl strategy is started. The spike occurs while the strategy goes through the Init_IO (initialize I/O) chart.

CAUSE

The spike may occur as a just started strategy transitions from its initial setpoint from host value (default value is 0), to the value set by the running strategy. In a PID where a lower setpoint indicates the output should increase, the setpoint temporarily going to zero would cause the output to go high in an effort to bring down the process variable. This would appear as a spike in the output.

WORKAROUND

In the ioControl Configurator Add PID Loop dialog, configure the Initial Value for the Setpoint from Host to its most common operating value. By doing so, there will be little or no spike when the strategy transitions form its initial starting value to the value set by the running strategy.

RESOLUTION

Opto 22 is aware of this issue.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None