‘Enable Communication to I/O Unit’ command and restoring I/O configuration in ioControl


Applies To:

SNAP-UP1-ADS
SNAP-UP1-M64
SNAP-UP1-D64
SNAP-LCE

Versions Affected:

Problem was discovered in version: Firmware R6.1a
Problem was corrected in version: Firmware R7.0a


Symptoms:

The Enable Communication to I/O Unit command in ioControl does not reconfigure an Ethernet I/O unit that has recovered from a power loss. When power is restored to the Ethernet I/O unit, the configuration is set to the default settings. This results, for example, in analog points not having proper scaling, and digital outputs that are configured as inputs.


Workaround:

Save the I/O unit configuration settings to the Flash EEPROM by including the Write I/O Unit Configuration to EEPROM command in an initialization chart in ioControl. The configuration is stored to the I/O unit’s permanent memory, eliminating the dependency on the control engine for configuration.


Resolution:

Opto 22 has corrected this issue.


Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.