How to configure the Windows XP firewall for ioManager and IP address configuration
Revision:  1.0
Published:  9/15/2006
Applies To
ioManager
SNAP-PAC-S1
SNAP-LCE
M4SENET-100
SNAP-B3000-ENET
SNAP-ENET-D64
SNAP-ENET-S64
Versions

PROCEDURE

Administrative or domain administrator privileges are required to perform the following operations. Domain administrators can configure these settings remotely and block the local machine administrator from modifying these settings.

  1. From Control Panel, select Windows Firewall. From the General tab, On turns on the firewall, and Off turns off the firewall.
  2. By default, the firewall blocks any application requesting the use of a system port below 1024. Opto 22 uses BOOTP to configure the IP Address. BOOTP is a UDP protocol that uses port 67 to receive requests.
  3. Once the firewall is enabled, click on the Exceptions tab. The following dialog box appears. Note, ioManager does not by default, appear in this dialog. This application must be added to the exceptions list.
  4. The exceptions list shown may be different based on prior configurations.

  5. To add ioManager to the exceptions list, click on Add Program. This brings up the available list of programs within the system. Highlight ioManager.
  6. If you have more than one ioManager entry, examine the Path text box for the correct executable path name.

  7. Click Change scope. Then select Any computer (including those on the Internet).

SUMMARY

Configuring IP addresses with ioManager sometimes presents problems due to the enabled Windows XP firewall. This article explains how to change the firewall settings to allow ioManager to configure Opto 22 Ethernet-based I/O units.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None