Improved true power readings at low current range from SNAP‑AIPM
Revision:  2.0
Published:  4/24/2006
Applies To
SNAP-AIPM
Versions

MORE INFORMATION

The following instructions explain the manufacture date code. Modules with a date code prior to JEXXXXXXEJ have not been updated, and require a return RMA. Modules with a special marking of ¢107 have been updated.

  1. The first two characters in the Build Code is the year of manufacture. The last two characters in the Build Code is the week of manufacture.

  2. The year and week is decoded by the following chart:

  3. 1 = A 3 = C 5 = E 7 = G 9 = I
    2 = B 4 = D 6 = F 8 = H 0 = J

The example below was manufactured in the year JE (05, which is 2005) and in week EJ (50, which is in December).

SYMPTOMS

At the low current range (less than 10% of the current range), the true power reading (from point 3) could sometimes exceed or be less than the calculated value (VRMS x ARMS) from VRMS (point 1) and ARMS (point 2).

CAUSE

Less resolution at the lower current range caused the above symptoms.

RESOLUTION

Opto 22 has corrected this issue. If you are experiencing the above symptoms, contact Opto 22 Product Support to discuss your system’s circumstances and to request a return RMA to correct your module.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None