KB54562
Unexpected ‘Ramp Analog Output’ PAC Control/ioControl command response if ramp endpoints are out of range
Revision:  3.0
Published:  7/5/2007
Applies To
SNAP-PAC-R1 Controller Firmware
SNAP-PAC-EB1 Brain Firmware
SNAP-UP1-ADS Controller/Brain Firmware
SNAP-UP1-M64
Versions
Problem was discovered in version:  
R8.0b SNAP PAC firmware
Problem was discovered in version:  
R7.1h Ultimate I/O firmware
Problem is fixed in version:  
R8.0c SNAP PAC firmware
Problem is fixed in version:  
R7.2d Ultimate I/O firmware

SYMPTOMS

For the PAC Control Ramp Analog Output command, if the ramp’s endpoints are set outside the range of the analog output module, then the analog output does not function correctly. The next Move command to the output causes the output to ramp to the position of the prior Ramp Analog Output command.

As an example, the problem may occur if the ramp endpoint for a 4 – 20 mA output point is set to 0 mA, or if the ramp endpoint for a 0 – 10 VDC output point is set to 12 VDC.

RESOLUTION

Opto 22 has resolved this issue.

Relevant Downloads
No relevant downloads have been specified.
Questions? Contact Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com

DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2016 Opto 22. All rights reserved.

My.Opto22

All Opto22

Request Information
  • FREE Product Brochure
  • Product Demonstration
  • PreSales Engineering Assistance

Opto 22 Product Support

Opto 22 Product Support is FREE Monday through Friday 7 a.m. to 5 p.m. Pacific Time

Product Support Numbers:

Local: (951) 695-3080
Toll-Free: (800) 835-6786
Fax: (951) 695-3017
support@opto22.com

Products

None

Downloads

None

Documents

None