AC Output, 12-140 VAC, 15 VDC Logic
$14.00 USD
Price in USA and Canada Only
Availability: In Stock
The OAC15 output module is used for controlling or switching AC loads of 12-140 VAC. Each module provides up to 4000 volts (transient) of optical isolation between the field devices and the control logic. This module is equivalent to a single pole, single throw, normally open contact (FORM A, SPST-NO, Make). All AC output modules feature zero voltage turn-on and zero current turn-off.
Typical uses and applications for AC output modules include switching the following loads:
- Relays
- Solenoids
- Motor starters
- Heaters
- Lamps or indicators
One Cycle
Surge
|
80 amps
peak
|
Peak Repetitive
Voltage
|
500 Volts
|
Operating
Ambient Temperature
|
-30 to
70 °C
|
Isolation,
Input-to-Output (Transient)
|
4,000 Vrms
|
Minimum
Load Current
|
20 milliamps
|
Operating
Frequency
|
25–65
Hz
|
Turn-on
Time
|
1/2 cycle
maximum-zero voltage
|
Turn-off
Time
|
1/2 cycle
maximum-zero current
|
DV/DT -
Off-State
|
200 volts/microseconds
|
DV/DT -
Commutating
|
Snubbed
for rated 0.5 power factor load
|
Output
Voltage Drop Maximum Peak
|
1.6 volts
|
Off-State
Leakage
@ Nominal Voltage - 60 Hz
|
5 milliamps rms
2.5 milliamps rms for OAC5A OAC15A,
and OAC24A @120 VAC
|
Module Specifications
|
Units
|
OAC5
|
OAC5A
|
OAC5H
|
OAC5A5
(NC)
|
OAC15
|
OAC15A
|
OAC24
|
OAC24A
|
OAC24H
|
Line Voltage
- Nominal
|
VAC
|
120
|
240
|
240
|
120/240
|
120
|
240
|
120
|
240
|
240
|
Operating
Voltage Range
|
VAC
|
12–140
|
24–280
|
24–280
|
24–280
|
12–140
|
24–280
|
12–140
|
24–280
|
24–280
|
Current
Rating
@ 45 °C Ambient
@ 70 °C Ambient
|
amps
amps
|
3
2
|
3
2
|
4
2
|
3
2
|
3
2
|
3
2
|
3
2
|
3
2
|
4
2
|
UL Motor
Load Rating
|
amps
|
1.5
|
1.5
|
-- *
|
1.5
|
1.5
|
1.5
|
1.5
|
1.5
|
-- *
|
Logic Voltage
- Nominal
|
VDC
|
5
|
5
|
5
|
5
|
15
|
15
|
24
|
24
|
24
|
Logic Voltage
Range (Vcc)**
|
VDC
|
2.5–8
|
2.5–8
|
2.5–8
|
2.5–8
|
9–16
|
9–16
|
18–32
|
18–32
|
18–32
|
Logic Pickup
Voltage*
|
VDC
|
2.5
|
2.5
|
2.5
|
2.5
|
9
|
9
|
18
|
18
|
18
|
Logic Dropout
Voltage
|
VDC
|
1
|
1
|
1
|
1
|
1
|
1
|
1
|
1
|
1
|
Logic Input
Current-@ Normal Logic
Voltage (Iout in schematic diagram)
|
mA
|
12
|
12
|
12
|
12
|
15
|
15
|
18
|
18
|
18
|
Control
Resistance
(Rc in schematic diagram)
|
Ohms
|
220
|
220
|
220
|
220
|
1K
|
1K
|
2.2K
|
2.2K
|
2.2K
|
*
Not UL approved
** Module only
|
|