SNAP-AIPM
|
SNAP-AIPM-3
|
Voltage Inputs (each
voltage channel)
|
Recommended Input Range
Scaled Input Range
|
85 to 250 VAC RMS
0 to 250 VAC RMS
|
85 to 250 VAC RMS
0 to 250 VAC RMS
|
Input Over Range
|
To 275 volts
|
To 275 volts
|
Resolution
|
10 mV
|
10 mV
|
Accuracy (47 to 63 Hz)
|
(When used within recommended
range)
± 0.2 V and ± 0.2% reading (at full scale = ± 0.7 V or
0.28%)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
|
(When used within recommended
range)
± 0.2 V and ± 0.2% reading (at full scale = ± 0.7 V or
0.28%)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
|
RMS Integration Time/
Data Freshness
|
1000 ms (synchronous
with current measurement)
|
1000 ms (synchronous
with current measurement)
|
Input Filtering
|
Time constant = 70 µs
(analog front end)
|
Time constant = 70 µs
(analog front end)
|
Input Resistance –
Single Ended
|
1 Megohm
NOTE: Because both channels share the same reference terminal, polarity must be observed when connecting the current channel.
|
1 Megohm
NOTE: Because both channels share the same reference terminal, polarity must be observed when connecting the current channel.
|
Maximum Input
|
300 V non-operating
|
300 V non-operating
|
Current Inputs (each
current channel)
|
Input Range
|
0 to 10 AC amps RMS
|
0 to 10 AC amps RMS
|
Input Over Range
|
To 11 amps (Reading is
not reliable over 11 A.)
|
To 11 amps (Reading is
not reliable over 11 A.)
|
Input Overload
|
15 A continuous, non-operating
|
15 A continuous, non-operating
|
Resolution
|
400 µA
|
400 µA
|
Accuracy (47 to 63 Hz)
|
± 8 mA and ±
0.2% reading (at full scale = ± 28 mA or 0.28%)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
|
± 8 mA and ±
0.2% reading (at full scale = ± 28 mA or 0.28%)
(–0.2 dB at 660 Hz; –3 dB at 1.89 kHz) nominal
|
RMS Integration Time/
Data Freshness
|
1000 ms (synchronous
with voltage measurement)
|
1000 ms (synchronous
with voltage measurement)
|
Input Filtering
|
Time constant = 105 µs
(analog front end)
|
Time constant = 105 µs
(analog front end)
|
Input Resistance –
Single Ended
|
0.005 Ohm
NOTE: Because both channels share the same reference terminal, polarity must be observed when connecting the voltage channel.
|
0.005 Ohm
NOTE: Because both channels share the same reference terminal, polarity must be observed when connecting the voltage channel.
|
Maximum Input
|
15 A continuous, non-operating
|
15 A continuous, non-operating
|
All Inputs (each
channel)
|
True Power and Volt-Amps
Range
|
True power: 2500.0 Watts.
Volt-amps: 2500.0 volt-amps
(inputs = 250 volts and 10 amps)
|
True power: 2500.0 Watts.
Volt-amps: 2500.0 volt-amps
(inputs = 250 volts and 10 amps)
|
Over Range
|
2750 Watts true power
or 27,500 counts volt-amps
|
2750 Watts true power
or 27,500 counts volt-amps
|
Accuracy:
|
|
|
True Power
Volt-Amps
|
± 0.6% reading (at
full scale = ± 15 Watts)
± 0.6% reading (at full scale = ± 15 VA)
|
± 0.6% reading (at
full scale = ± 15 Watts)
± 0.6% reading (at full scale = ± 15 VA)
|
Resolution
|
100 Megohms
|
100 Megohms
|
AC Common Mode Rejection
|
>– 120 dB at
60 Hz
|
>– 120 dB at
60 Hz
|
Maximum Operating Common
Mode Voltage
|
250 VAC
|
250 VAC
|
Power Requirements
|
5.0 VDC ± 0.15 VDC
at 100 mA
|
5.0 VDC ± 0.15 VDC
at 100 mA
|
Ambient Temperature:
|
|
|
Operating
Storage
|
0 to 70 °C
-25 to 85 °C
|
0 to 70 °C
-25 to 85 °C
|
Agency Approvals
|
CE, RoHS, DFARS
|
CE, RoHS, DFARS
|
Warranty
|
Lifetime
|
Lifetime
|
Calculated Outputs
|
True Power
|
0–2500 W (from
synchronous measurement of volts and amps)
|
0–2500 W (from
synchronous measurement of volts and amps)
|
Volt Amps
|
0–2500 VA (VRMS
x ARMS)
|
0–2500 VA (VRMS
x ARMS)
|
1-second E
|
n/a
|
0–7500 joules (true
power sum ABC, signed)
|
1-second abs E
|
n/a
|
0–7500 joules (true
power sum of absolute value of each A, B, and C, always positive)
|