SNAP-ODC-32-SRC
SNAP-ODC-32-SRC-FM
|
SNAP-ODC-32-SNK
SNAP-ODC-32-SNK-FM
|
Switching Voltage
|
5–60 VDC
|
5–60 VDC
|
Nominal Switching Voltage
|
12–24 VDC
|
12–24 VDC
|
Logic Voltage and Current
|
5 VDC ± 0.1
@ 150 mA
|
5 VDC ± 0.1
@ 150 mA
|
Maximum Off State Voltage
|
60 VDC
|
60 VDC
|
Output Leakage, Typical
|
<10 microamps per
channel (60 V, 70 °C)
|
<10 microamps per
channel (60 V, 70 °C)
|
Maximum Load per Point
|
0.25 A
|
0.25 A
|
Voltage Drop
|
0.15 VDC @ 0.25 A
|
0.15 VDC @ 0.25 A
|
Surge (1 sec.)
|
1 A
|
1 A
|
Output Arrangement
|
32 output channels; 4
groups of 8 outputs each. Points in each group share a common positive connection.
|
32 output channels; 4
groups of 8 outputs each. Points in each group share a common negative connection.
|
Output Turn-On/Off Time
|
100 microseconds
|
100 microseconds
|
Polling time from I/O
processor to module1
|
2–30 ms typical2
|
2–30 ms typical2
|
Indicators
|
None; use optional OptoTerminal-G20
diagnostic display or breakout rack.
|
None; use optional OptoTerminal-G20
diagnostic display or breakout rack.
|
Maximum Number of HDD
Modules on One Mounting Rack
|
16
|
16
|
Agency Approvals
|
SNAP-ODC-32-SRC: UL,
CE, RoHS, DFARS
SNAP-ODC-32-SRC-FM: CE, FM,
RoHS, DFARS
|
SNAP-ODC-32-SNK: UL,
CE, RoHS, DFARS
SNAP-ODC-32-SNK-FM: CE, FM,
RoHS, DFARS
|
Warranty
|
Lifetime
|
Lifetime
|
1 Affects
turn-on and turn-off determination
2 Time varies based on the SNAP PAC I/O processor (brain or on-the-rack
controller), processor configuration, and Ethernet host communication activity.
|