Some groov discrete input channels configured with On/Off totalization feature may return an invalid measurement


Applies To:

Firmware for the following groov I/O modules:

  • GRV-IAC-24
  • GRV-IACDCTTL-24
  • GRV-IACHV-24
  • GRV-IDC-24
  • GRV-IACI-12
  • GRV-IACIHV-12
  • GRV-IDCI-12
  • GRV-IDCSW-12
  • GRV-IDCIFQ-12

Versions Affected:

All versions prior to R1.3d of the following modules:

  • GRV-IAC-24
  • GRV-IACDCTTL-24
  • GRV-IACHV-24
  • GRV-IDC-24
  • GRV-IACI-12
  • GRV-IACIHV-12
  • GRV-IDCI-12
  • GRV-IDCSW-12
All versions prior to R1.3e of the following modules:
  • GRV-IDCIFQ-12

Resolved In Version:

R1.3d of the following modules:

  • GRV-IAC-24
  • GRV-IACDCTTL-24
  • GRV-IACHV-24
  • GRV-IDC-24
  • GRV-IACI-12
  • GRV-IACIHV-12
  • GRV-IDCI-12
  • GRV-IDCSW-12
R1.3e of the following modules:
  • GRV-IDCIFQ-12


Symptoms:

For the affected modules, if one or more channels is configured with the On/Off-time totalization feature, when the PAC Control command Get & Restart On/Off-Time Totalizer command retrieves the totalization value, on very rare occasions, the returned measurement may be an invalid value of 429496.7 seconds.

Workaround:

In the PAC Control strategy, add programming logic to filter out totalization measurements of 492496.7 seconds.

Resolution:

Opto 22 has resolved this issue.

Questions?

Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com


DISCLAIMER

This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.

OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.

OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.

Copyright © 2024 Opto 22. All rights reserved.