Analog input, temperature, ICTD, 12 channels

Production Specification

Part of the groov EPIC® system, the GRV-IICTD-12 analog input module collects temperature input data from any industry-standard Integrated Circuit Temperature Device (ICTD), such as the ICTD and ICTD-P3. The module has 12 channels of input. The module cover includes an LED that indicates status and a touch-sensitive pad. Touch the pad and the groov EPIC processor displays information about the module, including specifications and a wiring diagram.

The GRV-IICTD-12 mounts on a groov EPIC chassis with other analog, discrete, and serial groov I/O modules and a GRV-EPIC-PR1 processor. 

All groov I/O modules are UL/cUL listed and compliant with the ATEX, Low Voltage, and EMC CE and UKCA directives. Each module is factory tested twice before shipment and most modules are guaranteed for life.

Opto Products, like GRV-IICTD-12, are ideal for OEMs and machine designers, process control, machine monitoring, power and energy monitoring, predictive maintenance, remote installations like water-wastewater and oil & gas, SCADA, and industrial internet of things applications.

Features

GRV-IICTD-12

Number of Channels 12
Channel-to-Channel Isolation  
Analog Totalizing
Average Filter Weight
Minimum/Maximum Values
Offset and Gain
Quality Indication
Scaling
Simple Moving Average
 

Specification

GRV-IICTD-12

Input Range
-270.0 °C to 150 °C (-454.0 °F to 302 °F)
Input Range with ICTD Probe
-40.0 °C to 100 °C (-40.0 °F to 212 °F)
Input Range µA
3 to 425 µA
Over-range Limits
-270.0 °C to 150 °C (-454.0 °F to 302 °F)
Resolution
0.005 °C (0.0072 °F)
Accuracy with ICTD Probe
±0.8 °C (±1.4 °F)
Input Filter
-3 dB at 460 HZ
Software Data Filtering:
  • Simple Moving Average (SMA)
  • Weighted Average
 
  • 1 to 32 Readings
  • 1 to 4096
Data Refresh Time 450 ms
Step Input Response Time
450 ms x SMA value (14.4 s @ 32 SMA, Default SMA = 4 )
Analog Data Filtering
-3 dB @ 2.4 Hz / -25 dB @ 60 Hz
Common Mode Rejection
> -120 dB 
Quality Indications
out of range
Isolation (field-to-logic)
300 V working, 1500 V transient (1 minute)
Isolation (channel-to-channel)
None
Number of Channels
12
Chassis Power Consumption
1.0 W
Minimum groov EPIC Firmware Version
1.3.0
Minimum PAC Project Version 10.2000
Minimum Library Package for CODESYS Version 1.0.0.0
Wire Size
28–14 AWG
Wire Strip Length 0.315–0.354 inches (8–9 mm)
Torque, connector screw
2.5 in-lb (0.28 N-m)
Torque, hold-down screw
3.5 in-lb (0.4 N-m)
Temperature (operating)
-20 °C to +70 °C
Temperature (storage)
-40 °C to +85 °C
Relative Humidity (non-condensing)
5–95%
MTBF (minimum, 25 °C) 1.2 Mhrs
Agency Approvals
UL/cUL (Class 1, Div 2)a; CE: ATEX (Category 3, Zone 2) and RoHS; DFARS; CB Scheme; UKCA
Warranty
Lifetime
a For use in hazardous locations, equipment must be mounted in an enclosure that meets the requirements of the National Electrical Code, ANSI/NFPA 70, and ANSI/ISA-61010-1 (82.02.01).

Opto Products, like GRV-IICTD-12, are ideal for OEMs and machine designers, process control, machine monitoring, power and energy monitoring, predictive maintenance, remote installations like water-wastewater and oil & gas, SCADA, and industrial internet of things applications.

groov ICTD Temperature Input Module Data Sheet

The groov ICTD temperature input module, part number  GRV-IICTD-12, is part of Opto 22's groov EPIC® System. This document includes descriptions, specifications, and wiring and dimensional diagrams.

groov I/O Modules Firmware Release Notes

This document lists the latest updates to the firmware for groov I/O modules. It includes information on new features, enhancements, and bug fixes.

List of groov I/O module firmware download pages

Note: This document was formerly called a readme. The name was changed to more accurately describe its content.

UKCA Declaration of Conformity (groov EPIC and groov RIO)

This document is the Manufacturer's Declaration of Conformity for groov EPIC and groov RIO and their accessories, in accordance with the rules, regulations and standards of the United Kingdom. The models cited have been tested to the essential requirements listed in the Standards section, and fully comply with the legislation as listed in UK Legislation section.

ATEX Letter of Conformity for groov EPIC

This ATEX Letter of Conformity is provided to support CE Declaration of Conformity (groov EPIC and groov RIO), form 2261.

Declaration of Conformity (groov EPIC and groov RIO)

This document is the Manufacturer's Declaration of Conformity for the products listed herein, in accordance with European, international, and/or national standards and regulations.

GRV-IICTD-12 Module Firmware

This download contains current firmware for the GRV-IICTD-12 module. For a list of bug fixes and enhancements included in this firmware, see the groov I/O Modules Firmware Release Notes.

You can download previous versions of the firmware by clicking on the corresponding link: 1.3b1.3a

CAD Drawing: groov I/O Module

This ZIP file includes drawings in a variety of file formats (pdf, dwg, stp) that apply to all groov I/O modules.

Note: These drawings do not apply to groov RIO modules.

CAD Drawings: groov EPIC and groov RIO I/O wiring

This ZIP file contains I/O wiring diagrams for groov EPIC I/O modules and groov RIO models, in DWG format.

No videos or demos are available for this product.