ODC5P
Hover over image to zoom in

ODC5P

$24.50 (USA and Canada only)

Availability: In stock
Flat Pak output module, 5-60 VDC

Production Specification

Because of their low profile, Flat Pak modules are ideal for user-designed printed circuit boards where the standard single-channel or Quad Pak modules do not provide an exact fit.

The ODC5P handles 5-60 VDC. This module is used for controlling or switching DC loads. The module provides up to 4000 V of optical isolation between field inputs and the logic side of the circuit.

Typical uses and applications include switching the following loads:

  • DC relays
  • DC solenoids
  • DC motor starters
  • DC lamps or indicators

 

OAC5P

ODC5P

Operating Voltage Range

12–140 VAC

5–60 VDC

Line Voltage, Nominal

120 VAC

n/a

Current Rating

3 A @ 45 °C ambient

2 A @ 70 °C ambient

3 A @ 45 °C ambient

2 A @ 70 °C ambient

Off-state Leakage at Maximum Voltage

5 mA, rms

1 mA

Logic Voltage, Nominal

5 VDC

5 VDC

Logic Voltage Range (Vcc)

2.5–8 VDC

2.5–8 VDC

Logic Pickup Voltage

2.55 VDC

2.5 VDC

Logic Dropout Voltage

1 VDC

1 VDC

Logic Input Current at Normal Logic Voltage
(Iout in Schematic Diagram)

12 mA

12 mA

Control Resistance (Rc in Schematic Diagram)

220 Ohms

220 Ohms

One-second Surge

n/a

5 A

One-cycle Surge

80 A peak

n/a

Peak Repetitive Voltage

500 V

n/a

Minimum Load Current

20 mA

n/a

Operating Frequency

25–65 Hz

n/a

Turn-on Time

1/2 cycle maximum, zero voltage

100 microseconds

Turn-off Time

1/2 cycle maximum, zero current

750 microseconds

DV/DT, Off-state

200 V/microsecond

n/a

DV/DT, Commutating

Snubbed for rated 0.5 power factor load

n/a

Output Voltage Drop Maximum Peak

1.6 V

1.6 V

Operating Temperature

–30 to 70 °C

–30 to 70 °C

Agency Approvals

UL, CE, CSA; RoHS; UKCA

UL, CE, CSA; RoHS; UKCA

Warranty

Lifetime

Lifetime

Flat Pak I/O Module Data Sheet

Because of their low profile, Flat Pak modules are ideal for user-designed printed circuit boards where the standard single-channel or Quad Pak modules do not provide an exact fit.

Flat Pak modules include AC and DC input and output modules.

UKCA Declaration of Conformity (EMC, LVD, RoHS)

This document is the Manufacturer's Declaration of Conformity for the products listed herein, in accordance with the rules, regulations and standards of the United Kingdom. The models cited have been tested to the essential requirements listed in the Standards section, and fully comply with the legislation as listed in UK Legislation section.

Declaration of Conformity (EMC, LVD, RoHS)

This document is the Manufacturer's Declaration of Conformity for the products listed herein, in accordance with European, international, and/or national standards and regulations.

Opto 22 RoHS 3 Statement of Compliance - Restriction of Hazardous Substances

This document is a statement of compliance with the EU Directive 2015/863/EU, Restriction of Hazardous Substances (RoHS 3). This document lists Opto 22 products that comply with the substance restrictions of the RoHS 3 directive.

CSA Approval Document

This document lists all Opto 22 part numbers that have the Canadian Standards Association (CSA) approval.

UL Approval Document

This document lists all Opto 22 part numbers that have the Underwriters Laboratory (UL) approval.

CE Declaration: EMC

This document is the Manufacturer's Declaration for the listed products as mentioned in the attachment - to which this confirmation refers - that they are in accordance with the mentioned European, international and/or national standards and regulations.

CE Declaration: Low Voltage

This document is the Manufacturer's Declaration for the listed products as mentioned in the attachment - to which this confirmation refers - that they are in accordance with the mentioned European, international and/or national standards and regulations.

No downloads are available for this product.
No videos or demos are available for this product.