KB84077
Published: September 25, 2014
Revision: 1.0
Opening an earlier PAC Display project in Runtime R9.4a may incorrectly show 'No Data Source Configured' message
Applies To:
PAC Display Professional
Versions Affected:
Version affected: R9.4a
Problem is fixed in version: R9.4b
Resolved In Version:
Problem is fixed in version: R9.4b
Symptoms:
Opening an earlier PAC Display project in Runtime R9.4a may incorrectly show "No Data Source Configured" message. This issue can occur if the PAC Display project has either Operator Logging or SuperTrend Logging configured.
Workaround:
For Operator Logging: Configure the logging in Configure > Runtime > Security > Enable Runtime Operator Logging to specifically select a file for output rather than a data source.
For SuperTrend Logging: To save a SuperTrend log to a file, do the following:
-
Choose the Select tool and double-click the SuperTrend.
- Click Log To, and then select Log File from the pop-up menu to display the Historic Log File Configuration dialog box.
For details, see form 1702, the PAC Display User's Guide.
Resolution:
Opto 22 has resolved this issue.
Questions?
Contact: Opto 22 Product Support.
Phone: 800-835-6786 or 951-695-3080
Email: support@opto22.com
DISCLAIMER
This Opto 22 Knowledge Base ('OptoKB') article is intended to provide general technical information on a particular subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information in this OptoKB article is not intended to constitute application, design, software, or other professional engineering advice or services. Opto 22 may modify the OptoKB articles at any time. Before making any decision or taking any action which might affect your equipment, you should consult a qualified professional.
OPTO 22 DOES NOT WARRANT THE COMPLETENESS, TIMELINESS, OR ACCURACY OF THE DATA CONTAINED IN THIS OPTOKB ARTICLE AND MAY MAKE CHANGES THERETO AT ANY TIME AT ITS SOLE DISCRETION WITHOUT NOTICE. FURTHER, ALL INFORMATION CONVEYED HEREBY IS PROVIDED TO USERS 'AS IS.' IN NO EVENT SHALL OPTO 22 BE LIABLE FOR ANY DAMAGES OF ANY KIND INCLUDING DIRECT, INDIRECT INCIDENTAL, CONSEQUENTIAL, LOSS PROFIT, OR DAMAGE, EVEN IF OPTO 22 HAS BEEN ADVISED ON THE POSSIBILITY OF SUCH DAMAGES.
OPTO 22 DISCLAIMS ALL WARRANTIES WHETHER EXPRESSED OR IMPLIED WITH RESPECT TO THE INFORMATION (INCLUDING HARDWARE, SOFTWARE, AND/OR FIRMWARE) PROVIDED HEREBY, INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE, MERCHANTIBILITY, AND NON-INFRINGEMENT. Note that certain jurisdictions do not sanction the exclusion of implied warranties: thus, this disclaimer may not apply to you.
Copyright © 2024 Opto 22. All rights reserved.